SGL LNG gasification pressure regulating station characterized by high precision, compact structure, convenient installation, use and maintenance, and short construction period is applicable to the pressure regulation of gas used by users from cities and towns, communities or industrial areas and commercial areas where long-distance pipeline networks cannot be laid.
LNG, which can also be used as urban peak shaving equipment and standby equipment, is to purify and cool the gaseous natural gas, store and transport it at low temperature to the liquefied natural gas gasification station for gasification, pressure regulation, metering and odorization, and send it to the pipe network to supply it all kinds of users.
Process flow: the liquefied natural gas sent by the LNG tanker pressurizes the liquid in the tanker through the supercharger at the unloading position, and then it is charged into the LNG storage tank via the principle of differential pressure. When in use, the liquefied natural gas in the storage tank is pressurized by the self-pressurization system of the storage tank, or pressurized by the low-temperature pump, and then discharged to the LNG air temperature gasifier for gasification (the water bath heater shall be equipped in winter in northern China). Finally, the heated natural gas is regulated, measured, odorized and sent to the pipe network.
The liquefied natural gas in the unloading pipe connecting the LNG tanker and the LNG storage tank is evacuated by the EAG heater. If the pressure in the LNG storage tank is too high, it shall be vaporized by the BOG heater and then sent to the pre-pressure regulation system, or evacuated by the EAG heater.
Storage system: LNG low temperature storage tank (1-150m³) or LNG cryogenic insulation bottle group
Unloading system: Unloading supercharger, low-temperature corrugated hose
Gasification system: LNG air temperature gasifier, BOG air temperature heater, EAG air temperature heater and water-bath heater
Pressure regulating system: Pressure regulator
Metering system: Flowmeter
Odorization system: Gas odorizer
Control system: Central console
Applicable mediaLNG
Designed pressure1.76Mpa
Outlet pressure0.3-1.6Mpa
Outlet pressure0.1-0.4Mpa
Outlet temperatureLower than the ambient temperature by 5-10°C
Gasification capacity100-10000Nm³/h
Pressure regulationSelect two-way, three-way or multi-channel structure as required
Safety measuresOverpressure / pressure loss cut-off + safety release + gas leakage alarm
Metering equipmentSelect flowmeter with volume corrector as required
Purification equipment5μm, 10μm and 20μm can be selected for filter accuracy
Manual valveBall valve and butterfly valve (recommended for medium pressure)
Control valveSelect electric or pneumatic valve as needed
ReheaterSelect electric heating, hot water circulating heating or steam heating as required
OdorizerSelect as required
Data collectionCollect on-site pressure, temperature, differential pressure, flow, gas composition, equipment operation status and other parameters as required
Instrument air systemNitrogen cylinder and air compressor
Protective equipmentStainless steel outer box with strong corrosion resistance is recommended for color steel plate outer box and stainless steel outer box